Section 16
Monitoring
16.3.5
Table 406:
SSIML Group settings (basic)
Name
Values (Range)
Operation
Off
On
LevelAlmLimit
1.00 - 100.00
LevelLOLimit
1.00 - 100.00
TempAlarmLimit
-40.00 - 200.00
TempLOLimit
-40.00 - 200.00
tLevelAlarm
0.000 - 60.000
tLevelLockOut
0.000 - 60.000
tTempAlarm
0.000 - 60.000
tTempLockOut
0.000 - 60.000
tResetLevelAlm
0.000 - 60.000
tResetLevelLO
0.000 - 60.000
tResetTempLO
0.000 - 60.000
tResetTempAlm
0.000 - 60.000
530
Table 405:
SSIML Output signals
Name
Type
LOCKOUT
BOOLEAN
LVLLO
BOOLEAN
TEMPLO
BOOLEAN
ALARM
BOOLEAN
LVLALM
BOOLEAN
TEMPALM
BOOLEAN
LEVEL
REAL
TEMP
REAL

Settings

Unit
Step
-
-
-
0.01
-
0.01
-
0.01
-
0.01
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
s
0.001
Description
Level below lockout level or temperature above
lockout level
Level below lockout level
Temperature above lockout level
Level below alarm level or temperature above alarm
level
Level below alarm level
Temperature above alarm level
Level service value
Temperature of the insulation medium
Default
Description
Off
Operation Off / On
5.00
Alarm setting for level
3.00
Level lockout setting
30.00
Temperature alarm level setting of the
medium
30.00
Temperature lockout level of the medium
0.000
Time delay for level alarm
0.000
Time delay for level lockout indication
0.000
Time delay for temperature alarm
0.000
Time delay for temperture lockout
0.000
Reset time delay for level alarm
0.000
Reset time delay for level lockout
0.000
Reset time delay for temperture lockout
0.000
Reset time delay for temperture alarm
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6951-OUTPUTSIGNALS v7
PID-6951-SETTINGS v7
Technical manual