Technical Data - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 16
Monitoring
16.4.8
546
PRESALM
BLOCK
BLKALM
PRESLO
ANSI12000622 V1 EN-US
Figure 217:
Functional module diagram for circuit breaker gas pressure indication
When the PRESALM binary input is activated, the GPRESALM output is activated after
a time delay set with the tDGasPresAlm setting. The GPRESALM alarm can be blocked
by activating the BLKALM input.
If the pressure drops further to a very low level, the PRESLO binary input goes high,
activating the lockout alarm GPRESLO after a time delay set with the tDGasPresLO
setting. The GPRESLO alarm can be blocked by activating the BLKALM input.
The binary input BLOCK can be used to block the function. The activation of the
BLOCK input deactivates all outputs and resets internal timers. The alarm signals from
the function can be blocked by activating the binary input BLKALM.

Technical data

Table 414:
SSCBR Technical data
Function
Alarm level for open and close
travel time
Alarm level for number of
operations
Independent time delay for
spring charging time alarm
Independent time delay for gas
pressure alarm
Independent time delay for gas
pressure lockout
CB Contact Travel Time, opening
and closing
Remaining Life of CB
Accumulated Energy
tDGasPresAlm
AND
0
tDGasPresLO
AND
0
Range or value
(0 – 200) ms
(0 – 9999)
(0.00 – 60.00) s
(0.00 – 60.00) s
(0.00 – 60.00) s
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GPRESALM
GPRESLO
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v8
Accuracy
±3 ms
-
±0.2% or ±30 ms whichever is
greater
±0.2% or ±30 ms whichever is
greater
±0.2% or ±30 ms whichever is
greater
±3 ms
±2 operations
±1.0% or ±0.5 whichever is
greater
Technical manual