1MRK 511 408-UUS A
19.4.11
19.4.11.1
Phasor measurement unit RES670 2.2 ANSI
Technical manual
The input of this GOOSE block must be linked either in SMT by means
of a cross or in ACT by means of a GOOSE connection (if easy
GOOSE engineering is enabled) to receive the binary single point
values.
The implementation for IEC 61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
Horizontal communication via GOOSE for interlocking
GOOSEINTLKRCV
Functionality
GOOSE communication can be used for exchanging information between IEDs via the
IEC 61850-8-1 station communication bus. This is typically used for sending apparatus
position indications for interlocking or reservation signals for 1-of-n control. GOOSE
can also be used to exchange any boolean, integer, double point and analog measured
values between IEDs.
Section 19
Station communication
SEMOD173197-1 v2
GUID-92ECE152-892C-4214-95DE-B92718689434 v2
643