Function Block - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 16
Monitoring
16.10.3
590
BLOCK
RESET
IN
ADDTIME
tAddToTime
99 999.9 h
tWarning
tAlarm
-1
q
= unit delay
IEC15000321 V1 EN-US
Figure 234:
TEILGAPC logics
The main features of TEILGAPC are:
Applicable to very long time accumulation (≤ 99999.9 hours)
Supervision of limit transgression conditions and rollover/overflow
Possibility to define a warning and alarm with the resolution of 0.1 hours
Retain any saved accumulation value at a restart
Possibilities for blocking and reset
Possibility for manual addition of accumulated time
Reporting of the accumulated time

Function block

TEILGAPC
BLOCK
ALARM
IN
WARNING
ADDTIME
OVERFLOW
RESET
ACC_HOUR
ACC_DAY
IEC15000323.vsdx
IEC15000323 V1 EN-US
Figure 235:
TEILGAPC function block
Time Accumulation
with Retain
-1
q
a
a>b
b
a
a>b
b
a
a>b
b
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
ACC_HOUR
ACC_DAY
OVERFLOW
&
WARNING
&
ALARM
&
IEC15000321-1-en.vsd
GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1
Technical manual