1MRK 511 408-UUS A
Name
Values (Range)
I2-4>
1 - 2500
t4
0.000 - 60.000
TD4
0.05 - 999.00
IMin4
1.00 - 10000.00
t4Min
0.000 - 60.000
MultPU4
1.0 - 10.0
Table 109:
NS4PTOC (46I2) Group settings (advanced)
Name
Values (Range)
ResetTypeCrv1
Instantaneous
IEC Reset
ANSI reset
tReset1
0.000 - 60.000
tPCrv1
0.005 - 3.000
tACrv1
0.005 - 200.000
tBCrv1
0.00 - 20.00
tCCrv1
0.1 - 10.0
tPRCrv1
0.005 - 3.000
tTRCrv1
0.005 - 100.000
tCRCrv1
0.1 - 10.0
ResetTypeCrv2
Instantaneous
IEC Reset
ANSI reset
tReset2
0.000 - 60.000
tPCrv2
0.005 - 3.000
tACrv2
0.005 - 200.000
tBCrv2
0.00 - 20.00
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
%IB
1
17
s
0.001
1.200
-
0.01
0.05
%IB
1.00
17
s
0.001
0.000
-
0.1
2.0
Unit
Step
Default
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
-
0.1
1.0
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
-
Instantaneous
s
0.001
0.020
-
0.001
1.000
-
0.001
13.500
-
0.01
0.00
Current protection
Description
Negative sequence current op level for step 4
in % of IBase
Time delay of step 4 when definite time char.
is selected
Time multiplier for the step 4 selected time
characteristic
Minimum current for step 4
Minimum operate time for inverse time
characteristic step 4
Multiplier for scaling the current setting value
for step 4
Description
Reset curve type for step1 (Instantaneous /
IEC / ANSI)
Reset time delay for step 1
Param P for customized inverse trip time
curve for step 1
Param A for customized inverse trip time
curve for step 1
Param B for customized inverse trip time
curve for step 1
Param C for customized inverse trip time
curve for step 1
Param PR for customized inverse reset time
curve for step 1
Param TR for customized inverse reset time
curve for step
Param CR for customized inverse reset time
curve for step 1
Reset curve type for step2 (Instantaneous /
IEC / ANSI)
Reset time delay for step 2
Param P for customized inverse trip time
curve for step 2
Param A for customized inverse trip time
curve for step 2
Param B for customized inverse trip time
curve for step 2
Section 8