Section 13
Secondary system supervision
Table 208:
FUFSPVC Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 12
13.2.6
13.2.7
13.2.7.1
370
Unit
Step
-
1

Monitored data

Table 209:
FUFSPVC Monitored data
Name
Type
3I0
REAL
3I2
REAL
3V0
REAL
3V2
REAL
Operation principle
Zero and negative sequence detection
The zero and negative sequence function continuously measures the currents and
voltages in all three phases and calculates, see figure 130:
the zero-sequence voltage 3V0
the zero-sequence current 3I0
the negative sequence current 3I2
the negative sequence voltage 3V2
The measured signals are compared with their respective set values 3V0PU and 3I0PU,
3V2PU and 3I2PU.
The function enable the internal signal FuseFailDetZeroSeq if the measured zero-
sequence voltage is higher than the set value 3V0PU and the measured zero-sequence
current is below the set value 3I0PU.
The function enable the internal signal FuseFailDetNegSeq if the measured negative
sequence voltage is higher than the set value 3V2PU and the measured negative
sequence current is below the set value 3I2PU.
Default
Description
1
Selection of one of the Global Base Value
groups
Values (Range)
Unit
-
A
-
A
-
kV
-
kV
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3492-MONITOREDDATA v8
Description
Magnitude of zero sequence
current
Magnitude of negative
sequence current
Magnitude of zero sequence
voltage
Magnitude of negative
sequence voltage
M13677-3 v5
Technical manual