Current protection
8.3.3
214
All IEC and ANSI time delayed characteristics are available together with an optional
user defined characteristic.
The directional function is voltage polarized.
NS4PTOC (4612) can be set directional or non-directional independently for each of
the steps.
NS4PTOC (4612) can be used as main protection for unsymmetrical fault; phase-phase
short circuits, phase-phase-ground short circuits and single phase ground faults.
NS4PTOC (4612) can also be used to provide a system backup for example, in the case
of the primary protection being out of service due to communication or voltage
transformer circuit failure.
Directional operation can be combined together with corresponding communication
logic in permissive or blocking teleprotection scheme. The same logic as for
directional zero sequence current can be used. Current reversal and weak-end infeed
functionality are available.