1MRK 511 408-UUS A
19.5.4
Table 498:
MU1_HW Non group settings (basic)
Name
Values (Range)
CTStarPoint1
FromObject
ToObject
CTStarPoint2
FromObject
ToObject
CTStarPoint3
FromObject
ToObject
CTStarPoint4
FromObject
ToObject
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
SMPLLOST
BOOLEAN
MUSYNCH
BOOLEAN
TESTMODE
BOOLEAN
SIMMODE
BOOLEAN
I1QUALITY
INTEGER
I2QUALITY
INTEGER
I3QUALITY
INTEGER
I4QUALITY
INTEGER
U1QUALITY
INTEGER
U2QUALITY
INTEGER
U3QUALITY
INTEGER
U4QUALITY
INTEGER

Settings

Unit
Step
-
-
-
-
-
-
-
-
Station communication
Description
Fatal error or recovery state after fatal error. High if
any subscribed channel has bad quality or TEST while
IED not in test mode.
MU not synced or MU clock not synced to same clock
as IED
Quality of one or more subscribed analogue channels
is TEST
MU delivers simulated data accepted by IED
Binary coded quality information for I1
Binary coded quality information for I2
Binary coded quality information for I3
Binary coded quality information for I0
Binary coded quality information for VA
Binary coded quality information for VB
Binary coded quality information for VC
Binary coded quality information for 3V0
Default
Description
ToObject
ToObject= towards protected object,
FromObject= the opposite
ToObject
ToObject= towards protected object,
FromObject= the opposite
ToObject
ToObject= towards protected object,
FromObject= the opposite
ToObject
ToObject= towards protected object,
FromObject= the opposite
Section 19
SEMOD166625-1 v2
PID-6850-SETTINGS v3
653