The output ALARM goes high if the pressure alarm condition or the temperature alarm
condition exists inside the circuit breaker. The output ALARM can be blocked by
activating BLOCK or BLKALM inputs.
The output LOCKOUT goes high if the pressure lockout condition or the temperature
lockout condition exists inside the circuit breaker and it resets by using the binary input
RESETLO. The output LOCKOUT can be blocked by activating BLOCK input.

Technical data

Table 403:
SSIMG (63) Technical data
Function
Pressure alarm level
Pressure lockout level
Temperature alarm level
Temperature lockout level
Time delay for pressure alarm
Reset time delay for pressure
alarm
Time delay for pressure lockout
Time delay for temperature alarm
Reset time delay for temperature
alarm
Time delay for temperature
lockout
Liquid medium supervision SSIML (71)
Identification
Function description
Insulation liquid monitoring function
Range or value
1.00-100.00
1.00-100.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
SSIML
-
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v7
Accuracy
±10.0% of set value
±10.0% of set value
±2.5% of set value
±2.5% of set value
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
GUID-37669E94-4830-4C96-8A67-09600F847F23 v3
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3
ANSI/IEEE C37.2
device number
71