Table 493:
GOOSEINTLKRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
19.4.11.5
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
APP15VAL
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN

Settings

Unit
Step
-
-
Operation principle
The APPxVAL output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and communication
error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
At least one of the inputs of this GOOSE block must be linked either in
SMT by means of a cross or in ACT by means of a GOOSE connection
Station communication
Description
Apparatus 15 position is valid
Communication Valid
Test Output
Default
Description
Disabled
Operation Disabled/Enabled
Data Value
Data Valid
Updated
1
0
0
0
0
0
0
0
0
0
0
0
0
Updated
1
Updated
1
0
0
Section 19
SEMOD173168-1 v2
PID-6831-SETTINGS v3
GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
1
0
0
0
1
0
1
1
0
0