Signals - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 10
Frequency protection
10.1.4
10.1.5
Table 164:
SAPTUF (81L) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PUFrequency
35.00 - 75.00
IntBlockLevel
0.0 - 100.0
tDelay
0.000 - 60.000
tReset
0.000 - 60.000
tRestore
0.000 - 60.000
RestoreFreq
45.00 - 65.00
TimerMode
Definite timer
Volt based timer
VNom
50.0 - 150.0
VMin
50.0 - 150.0
Table continues on next page
302

Signals

Table 162:
SAPTUF (81L) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTRIP
BOOLEAN
BLKREST
BOOLEAN
Table 163:
SAPTUF (81L) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
RESTORE
BOOLEAN
BLKDMAGN
BOOLEAN
FREQ
REAL
Settings
Unit
Step
-
-
Hz
0.01
%VB
1.0
s
0.001
s
0.001
s
0.001
Hz
0.01
-
-
%VB
1.0
%VB
1.0
Default
Description
-
Three phase group signal for voltage inputs
0
Block of function
0
Blocking operate output
0
Blocking restore output
Description
Common trip signal
Common pickup signal
Restore signal for load restoring purposes
Blocking indication due to low magnitude
Measured frequency
Default
Description
Disabled
Operation Disabled/Enabled
48.80
Frequency set value
50.0
Internal blocking level in % of VBase
0.200
Operate time delay
0.000
Time delay for reset
0.000
Restore time delay
49.90
Restore frequency value
Definite timer
Setting for choosing timer mode
100.0
Nominal voltage for voltage based timer in %
of UBase
90.0
Lower operation limit for voltage based timer
in % of VBase
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6752-INPUTSIGNALS v2
PID-6752-OUTPUTSIGNALS v2
PID-6752-SETTINGS v2
Technical manual