15.14.7
15.15
15.15.1
15.15.2
Phasor measurement unit RES670 2.2 ANSI
Technical manual
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted to boolean by
the ITBGAPC function block.
The operator position input (PSTO) determines the operator place. The integer number
that is communicated to the ITBGAPC can only be written to the block while the
PSTO is in position "Remote". If PSTO is in position "Off" or "Local", then no
changes are applied to the outputs.

Technical data

Table 348:
Number of ITBGAPC instances
Function
3 ms
ITBGAPC
4
Elapsed time integrator with limit transgression and
overflow supervision TEIGAPC
Identification
Function Description
Elapsed time integrator
Functionality
Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the
elapsed time when a given binary signal has been high, see also Figure 185.
Quantity with cycle time
8 ms
4
IEC 61850
IEC 60617
identification
identification
TEIGAPC
-
Section 15
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v1
100 ms
8
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3
ANSI/IEEE C37.2 device
number
-
GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3
Logic
475