22.12
22.12.1
22.12.2
Phasor measurement unit RES670 2.2 ANSI
Technical manual

Functionality

Global base values function (GBASVAL) is used to provide global values, common for
all applicable functions within the IED. One set of global values consists of values for
current, voltage and apparent power and it is possible to have twelve different sets.
This is an advantage since all applicable functions in the IED use a single source of
base values. This facilitates consistency throughout the IED and also facilitates a single
point for updating values when necessary.
Each applicable function in the IED has a parameter, GlobalBaseSel, defining one out
of the twelve sets of GBASVAL functions.
Settings
Unit
Step
kV
0.05
A
1
MVA
0.05
Primary system values PRIMVAL
Identification
Function description
Primary system values
Functionality
The rated system frequency and phase rotation direction are set under Main menu/
Configuration/ Power system/ Primary Values in the local HMI and PCM600
parameter setting tree.
Default
Description
400.00
Global base voltage
3000
Global base current
2000.00
Global base apparent power
IEC 61850
IEC 60617
identification
identification
PRIMVAL
-
Section 22
Basic IED functions
GUID-D58ECA9A-9771-443D-BF84-8EF582A346BF v4
GUID-C73A66FB-5D6E-4DC3-B8B5-046AEC2F1FDE v1
PID-4026-SETTINGS v7
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
ANSI/IEEE C37.2
device number
-
M15288-3 v6
795

Advertisement

Table of Contents
loading

Table of Contents