Communication Interfaces And Protocols - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
19.4.2
19.4.3
Table 469:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
GOOSEPortEd1
AP_FRONT
AP_1
AP_2
AP_3
AP_4
AP_5
AP_6
Protocol Edition
Ed 1
Ed 2
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
communication over MMS are supported. Disturbance recording file (COMTRADE)
uploading can be done over MMS or FTP.
The front port is only intended for PCM600 communication,
maintenance, training and test purposes due to risk of interference
during normal operation.

Communication interfaces and protocols

Table 468:
Supported station communication interfaces and protocols
Protocol
Ethernet
IEC 61850–8–1
DNP3
IEC 60870-5-103
● = Supported
When double Ethernet ports are activated, make sure that all ports are
connected to different subnets. For example: port 1 has IP address
198.168.101.10 with subnet mask 255.255.255.0, and port 2 has IP
address 198.168.102.10 with subnet mask 255.255.255.0.
Settings
Unit
Step
-
-
-
-
-
-
100BASE-FX (ST
Glass fibre (ST connector)
connector)
-
Default
Disabled
AP_1
Ed 1
Section 19
Station communication
GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v7
Serial
-
Description
Operation Disabled/Enabled
Selection of GOOSE port (only for IEC61850
Ed1)
Protocol Edition
EIA-485
-
PID-6702-SETTINGS v3
627

Advertisement

Table of Contents
loading