Limit Counter L4Ufcnt - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.9
16.9.1
16.9.1.1
16.9.2
16.9.3
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Table 433:
Input integer value converted to binary output signals
Measured supervised
below low-low
value is:
limit
Output:
LOWLOW
High
LOW
NORMAL
HIGH
HIGHHIGH

Limit counter L4UFCNT

Identification
Identification
Function description
Limit counter
Functionality
The 12 Up Limit counter (L4UFCNT) provides a settable counter with four
independent limits where the number of positive and/or negative sides on the input
signal are counted against the setting values for limits. The output for each limit is
activated when the counted value reaches that limit.
Overflow indication is included for each up-counter.
Operation principle
Limit counter (L4UFCNT) counts the number of positive and/or negative sides on the
binary input signal depending on the function settings. L4UFCNT also checks if the
accumulated value is equal or greater than any of its four settable limits. The four limit
outputs will be activated relatively on reach of each limit and remain activated until the
reset of the function. Moreover, the content of L4UFCNT is stored in flash memory
and will not be lost at an auxiliary power interruption.
between low‐
between low
low and low
and high limit
limit
High
High
IEC 61850
IEC 60617
identification
identification
L4UFCNT
Section 16
Monitoring
between high-
above high-high
high and high
limit
limit
High
High
GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1
GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v2
ANSI/IEEE C37.2
device number
-
GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6
GUID-4D58423F-329C-4553-9FAF-E55A368849A5 v2
585