ABB RES670 Technical Manual page 339

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Table 186:
CVGAPC Group settings (advanced)
Name
Values (Range)
MultPU_OC1
1.0 - 10.0
ResCrvType_OC1
Instantaneous
IEC Reset
ANSI reset
tResetDef_OC1
0.00 - 6000.00
P_OC1
0.001 - 10.000
A_OC1
0.000 - 999.000
B_OC1
0.000 - 99.000
C_OC1
0.000 - 1.000
PR_OC1
0.005 - 3.000
TR_OC1
0.005 - 600.000
CR_OC1
0.1 - 10.0
MultPU_OC2
1.0 - 10.0
ResCrvType_OC2
Instantaneous
IEC Reset
ANSI reset
tResetDef_OC2
0.00 - 6000.00
P_OC2
0.001 - 10.000
A_OC2
0.000 - 999.000
B_OC2
0.000 - 99.000
C_OC2
0.000 - 1.000
PR_OC2
0.005 - 3.000
TR_OC2
0.005 - 600.000
CR_OC2
0.1 - 10.0
tResetDef_UC2
0.00 - 6000.00
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
0.1
2.0
-
-
Instantaneous
s
0.01
0.00
-
0.001
0.020
-
0.001
0.140
-
0.001
0.000
-
0.001
1.000
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
-
0.1
2.0
-
-
Instantaneous
s
0.01
0.00
-
0.001
0.020
-
0.001
0.140
-
0.001
0.000
-
0.001
1.000
-
0.001
0.500
-
0.001
13.500
-
0.1
1.0
s
0.01
0.00
Section 11
Multipurpose protection
Description
Multiplier for scaling the current setting value
for OC1
Selection of reset curve type for OC1
Reset time delay used in IEC Definite Time
curve OC1
Parameter P for customer programmable
curve for OC1
Parameter A for customer programmable
curve for OC1
Parameter B for customer programmable
curve for OC1
Parameter C for customer programmable
curve for OC1
Parameter PR for customer programmable
curve for OC1
Parameter TR for customer programmable
curve for OC1
Parameter CR for customer programmable
curve for OC1
Multiplier for scaling the current setting value
for OC2
Selection of reset curve type for OC2
Reset time delay used in IEC Definite Time
curve OC2
Parameter P for customer programmable
curve for OC2
Parameter A for customer programmable
curve for OC2
Parameter B for customer programmable
curve for OC2
Parameter C for customer programmable
curve for OC2
Parameter PR for customer programmable
curve for OC2
Parameter TR for customer programmable
curve for OC2
Parameter CR for customer programmable
curve for OC2
Reset time delay used in IEC Definite Time
curve UC2
333