Section 16
Monitoring
16.8.3
16.8.4
16.8.5
584

Function block

RANGE_XP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC05000346-2-en.vsd
IEC05000346 V2 EN-US
Figure 230:
RANGE_XP function block
Signals
Table 431:
RANGE_XP Input signals
Name
Type
RANGE
INTEGER
Table 432:
RANGE_XP Output signals
Name
Type
HIGHHIGH
BOOLEAN
HIGH
BOOLEAN
NORMAL
BOOLEAN
LOW
BOOLEAN
LOWLOW
BOOLEAN
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The
function block converts the input integer value to five binary output signals according
to
table
433.
Default
Description
0
Measured value range
Description
Measured value is above high-high limit
Measured value is between high and high-high limit
Measured value is between high and low limit
Measured value is between low and low-low limit
Measured value is below low-low limit
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
SEMOD54336-4 v3
SEMOD53803-1 v2
PID-3819-INPUTSIGNALS v5
PID-3819-OUTPUTSIGNALS v5
SEMOD52462-4 v5
Technical manual