Advertisement

Section 8
Current protection
206
Characteristic
for PUREV
-RCA +85 deg
RCA -85 deg
Characteristic for forward
release of measuring steps
ANSI11000243 V1 EN-US
Figure 60:
Operating characteristic for ground-fault directional element using the
zero sequence components
The relevant setting parameters for the directional supervision element are:
The directional element will be internally enabled to trip as soon as Iop is bigger
than 40% of IDirPU and the directional condition is fulfilled in the set direction.
The relay characteristic angle AngleRCA, which defines the position of forward
and reverse areas in the operating characteristic.
The directional comparison will set the output binary signals:
1.
PUFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger
than setting parameter IDirPU and directional supervision element detects fault in
forward direction.
2.
PUREV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger
than 60% of setting parameter IDirPU and directional supervision element detects
fault in reverse direction.
Operating area
PUREV
0.6 * INDirPU
Characteristic for reverse
release of measuring steps
40% of
INDirPU
RCA
65°
I
= 3I
op
Operating area
Characteristic
for PUFW
1MRK 511 408-UUS A
-RCA -85 deg
VPol = -3V
INDirPU
PUFW
0
ANSI11000243-1-en.ai
Phasor measurement unit RES670 2.2 ANSI
Technical manual
RCA +85 deg
0