Design - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 10
Frequency protection
10.3.6.4
316
BLOCK:
blocks the START and TRIP outputs
BLKTRIP:
blocks the TRIP output
BLKREST:
blocks the RESTORE output
If the measured voltage level decreases below the setting of IntBlockLevel, both the
PICKUP and the TRIP outputs are blocked.

Design

Rate-of-change frequency protection (SAPFRC, 81) measuring element continuously
measures the frequency of the selected voltage and compares it to the setting
PUFreqGrad. The frequency signal is filtered to avoid transients due to power system
switchings and faults. The time integrator operates with a definite delay time. When
the frequency has returned back to the setting of RestoreFreq, the RESTORE output is
issued after the time delay tRestore, if the TRIP signal has earlier been issued. The sign
of the setting PUFreqGrad is essential, and controls if the function is used for raising
or lowering frequency conditions. The design of SAPFRC (81) is schematically
described in figure 110.
1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
M14970-34 v7