Section 11
Multipurpose protection
52
ANSI05000169 V2 EN-US
Figure 119:
Treatment of measured currents and voltages within IED for CVGAPC function
346
ADM
Figure
119
shows how internal treatment of measured currents is done for
multipurpose protection function
The following currents and voltages are inputs to the multipurpose protection function.
They must all be expressed in true power system (primary) Amperes and kilovolts.
1.
Instantaneous values (samples) of currents & voltages from one three-phase
current and one three-phase voltage input.
2.
Fundamental frequency phasors from one three-phase current and one three-phase
voltage input calculated by the pre-processing modules.
3.
Sequence currents & voltages from one three-phase current and one three-phase
voltage input calculated by the pre-processing modules.
The multipurpose protection function:
CVGAPC function
Current and voltage selection
settings
Selection of which current
and voltage shall be given to
the built-in protection
elements
Restraint current selection
Selected restraint current
Selection of restraint current
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
IED
Selected current
Selected voltage
ANSI05000169_2_en.vsd
Technical manual