ABB RES670 Technical Manual page 511

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Table 383:
VMSQI Non group settings (basic)
Name
Values (Range)
3V0DbRepInt
1 - 100000
3V0ZeroDb
0 - 100000
3V0Min
0.0 - 200.0
3V0Max
0.0 - 200.0
GlobalBaseSel
1 - 12
3V0RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
3V0LimHys
0.000 - 100.000
3V0AngDbRepInt
1 - 100000
Operation
Disabled
Enabled
V1DbRepInt
1 - 100000
V1ZeroDb
0 - 100000
V1Min
0.0 - 200.0
V1Max
0.0 - 200.0
V1RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
V1LimHys
0.000 - 100.000
V1AngDbRepInt
1 - 100000
V2DbRepInt
1 - 100000
V2ZeroDb
0 - 100000
V2Min
0.0 - 200.0
V2Max
0.0 - 200.0
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
Type
1
10
m%
500
1000
%VB
0.1
50.0
%VB
0.1
200.0
-
1
1
-
-
Cyclic
%
0.001
5.000
s
1
10
-
-
Disabled
Type
1
10
m%
500
1000
%VB
0.1
50.0
%VB
0.1
200.0
-
-
Cyclic
%
0.001
5.000
s
1
10
Type
1
10
m%
500
1000
%VB
0.1
50.0
%VB
0.1
200.0
Section 16
Monitoring
Description
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
Minimum value in % of VBase
Maximum value in % of VBase
Selection of one of the Global Base Value
groups
Reporting type
Hysteresis value in % of range, common for
all limits
Cyclic report interval (s)
Disbled/Enabled operation
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
Minimum value in % of VBase
Maximum value in % of VBase
Reporting type
Hysteresis value in % of range, common for
all limits
Cyclic report interval (s)
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
Minimum value in % of VBase
Maximum value in % of VBase
PID-6739-SETTINGS v2