Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 12
System protection and control
12.1.5
Table 196:
SMAIHPAC Non group settings (basic)
Name
Values (Range)
ConnectionType
Ph - Ph
Ph - N
SetFrequency
2.0 - 500.0
FreqBandWidth
0.0 - 60.0
FilterLength
0.1 s
0.2 s
0.5 s
1.0 s
2.0 s
4.0 s
OverLap
0 - 95
12.1.6
356
Table 195:
SMAIHPAC Output signals
Name
Type
AI3P
GROUP SIGNAL
AI1
GROUP SIGNAL
AI2
GROUP SIGNAL
AI3
GROUP SIGNAL
AI4
GROUP SIGNAL

Settings

Unit
Step
-
-
Hz
0.1
Hz
0.1
-
-
%
5
Operation principle
For all four analogue input signals into this filter (i.e. three phases and the residual
quantity) the input samples from the TRM module which are coming at rate of 20
samples per fundamental system cycle are first stored. When enough samples are
available in the internal memory, the phasor values at set frequency defined by the
setting parameter SetFrequency are calculated. The following values are internally
available for each of the calculated phasors:
Magnitude
Phase angle
Exact frequency of the extracted signal
Description
Analog input 3-phase group
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Default
Description
Ph - N
Analogue input connection type
50.0
Desired frequency to be extracted by the filter
0.0
Extra added frequency band around the set
frequency
1.0 s
Approximate length of the filtering window in
seconds
20
Filtering window overlap between two
calculations in percent
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6733-OUTPUTSIGNALS v1
GUID-5EA398AD-66E2-4240-8918-4332995CED11 v1
PID-6733-SETTINGS v1
GUID-262C1783-3A0A-46B6-99FC-1202AE8E7519 v2
Technical manual