Ied Identifiers Terminalid - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
22.4
22.4.1
22.4.2
Table 603:
TERMINALID Non group settings (basic)
Name
Values (Range)
StationName
0 - 18
StationNumber
0 - 99999
ObjectName
0 - 18
ObjectNumber
0 - 99999
UnitName
0 - 18
UnitNumber
0 - 99999
IEDMainFunType
0 - 255
TechnicalKey
0 - 16
0 - 16
0 - 16
0 - 16
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Each of the functions includes the blocking from the TESTMODE function block.
The functions can also be blocked from sending events over IEC 61850 station bus to
prevent filling station and SCADA databases with test events, for example during a
commissioning or maintenance test.

IED identifiers TERMINALID

Functionality
IED identifiers (TERMINALID) function allows the user to identify the individual IED
in the system, not only in the substation, but in a whole region or a country.
Use only characters A-Z, a-z and 0-9 in station, object and unit names.
Settings
Unit
Step
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
-
1
Default
Description
Station name
Station name
0
Station number
Object name
Object name
0
Object number
Unit name
Unit name
0
Unit number
0
IED main function type for IEC60870-5-103
AA0B0Q0A0
Technical key (part 1)
Technical key (part 2)
Technical key (part 3)
Technical key (part 4)
Section 22
Basic IED functions
IP15060-1 v2
M15324-3 v6
GUID-3C49A222-FFE4-492B-A96C-9E9965FA2CB4 v2
PID-6801-SETTINGS v1
779