Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
15.7.7.3
Table 277:
RSMEMORY Group settings (basic)
Name
Values (Range)
Memory
Disabled
Enabled
15.7.7.4
15.7.8
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Table 276:
RSMEMORY Output signals
Name
Type
OUT
BOOLEAN
NOUT
BOOLEAN

Settings

Unit
Step
-
-
Technical data
Table 278:
Number of RSMEMORY instances
Logic block
3 ms
RSMEMORY
10
Set-reset with memory function block SRMEMORY
The Set-reset with memory function block (SRMEMORY) is a flip-flop with memory
that can set or reset an output from two inputs respectively. Each SRMEMORY
function block has two outputs, where one is inverted. The memory setting controls if,
after a power interruption, the flip-flop resets or returns to the state it had before the
power interruption. The input SET has priority.
Table 279:
Truth table for SRMEMORY function block
SET
RESET
OUT
0
0
Last
value
0
1
0
1
0
1
1
1
1
Description
Output signal
Inverted output signal
Default
Description
Enabled
Operating mode of the memory function
Quantity with cycle time
8 ms
10
NOUT
Inverted
last value
1
0
0
Section 15
Logic
PID-3811-OUTPUTSIGNALS v5
PID-3811-SETTINGS v5
GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v1
100 ms
20
IP11020-1 v2
M11485-3 v4
439

Advertisement

Table of Contents
loading