1MRK 511 408-UUS A
Name
Values (Range)
DirModeSel2
Disabled
Non-directional
Forward
Reverse
Characterist2
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-2>
1 - 2500
t2
0.000 - 60.000
TD2
0.05 - 999.00
IMin2
1.00 - 10000.00
t2Min
0.000 - 60.000
MultPU2
1.0 - 10.0
DirModeSel3
Disabled
Non-directional
Forward
Reverse
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
-
-
Non-directional
-
-
ANSI Def. Time
%IB
1
50
s
0.001
0.400
-
0.01
0.05
%IB
1.00
50
s
0.001
0.000
-
0.1
2.0
-
-
Non-directional
Current protection
Description
Directional mode of step 2 (Disabled, Nondir,
Forward, Reverse)
Time delay characteristic for step 2
Negative sequence current op level for step 2
in % of IBase
Time delay of step 2 when definite time char.
is selected
Time multiplier for the step 2 selected time
characteristic
Minimum current for step 2
Minimum operate time for inverse time
characteristic step 2
Multiplier for scaling the current setting value
for step 2
Directional mode of step 3 (Disabled, Nondir,
Forward, Reverse)
Section 8
217