1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Device 1
AP1
PhyPortA
PhyPortB
Switch A
PhyPortA
PhyPortB
AP1
Device 3
IEC09000758 V4 EN-US
Figure 249:
Redundant station bus
IEC 62439-3 High-availabillity Seamless Redundancy (HSR)
HSR applies the principle of parallel operation to a single ring.
For each message sent, the node sends two frames, one through each port. Both the
frames circulate in opposite directions over the ring. Every node forwards the frames it
receives from one port to another to reach the next node. When the originating sender
node receives the frame it sent, the sender node discards the frame to avoid loops
The RCHLCCH function block supervise the redundant communication on the two
channels. If no data package has been received on one (or both) channels within the
last 10 s, the output LinkAUp and/or LinkBUp is set to 0 which indicates an error.
If IEEE1588 (PTP) is used an accuracy of 1 µs can be guaranteed for up to 15 devices
in one HSR-ring.
Device 2
AP1
PhyPortA
PhyPortB
Switch B
PhyPortA
PhyPortB
AP1
Device 4
IEC09000758-4-en.vsd