Enable Forcing Using Testmode Function Block; How To Change Binary Input/Output Signals Using Forcing; Forcing By Using Lhmi - ABB RES670 2.1 Commissioning Manual

Phasor measurement unit
Table of Contents

Advertisement

Section 10
Testing IED operation
10.8.2.2
10.8.3
10.8.3.1
90
IEC15000029 V1 EN
2.
Exit back to the root menu.
3.
Select Yes in the save dialogue box.
Once the IED is in test mode the yellow Start LED starts to blink.

Enable forcing using TESTMODE function block

Use the TESTMODE function block, appropriately configured in PCM600/ACT.
It may be convenient to control the input on mentioned component from, for example, an
LHMI function key or similar during commissioning to quickly and easily enter IED test
mode.

How to change binary input/output signals using forcing

Once the IED is in IED test mode, the LHMI/PCM600 menus can be used to control input/
output signals freely.

Forcing by using LHMI

Editing a signal value directly
Edit the input/output value directly to select the desired logical level, by doing
following:
1.
Select the value line of the desired signal, see figure 22.
2.
Press the Enter key to edit the value.
1MRK 511 366-UUS -
Commissioning manual