ABB RES670 Technical Manual page 298

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 9
Voltage protection
292
where:
Vpickup
Set value for step 1 and step 2
>
V
Measured voltage
The type B curve is described as:
TD
480
t
=
+
V Vpickup
>
32
0 5
.
Vpickup
>
ANSIEQUATION2287 V3 EN-US
The type C curve is described as:
TD
480
=
+
t
>
V Vpickup
32
0 5
.
>
Vpickup
ANSIEQUATION2288 V2 EN-US
The customer programmable curve is defined by the below equation, where A, B, C, D,
k and p are settings:
×
TD A
=
t
æ
ö
-
V Vpickup
×
-
ç
÷
B
C
è
ø
Vpickup
EQUATION1616 V1 EN-US
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set
to compensate for this phenomenon. In the voltage interval Vpickup up to Vpickup ·
(1.0 + CrvSatn/100) the used voltage will be: Vpickup · (1.0 + CrvSatn/100). If the
programmable curve is used this parameter must be calculated so that:
CrvSatn
×
-
>
B
C
0
100
EQUATION1435 V1 EN-US
The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
integration, see figure 97. The details of the different inverse time characteristics are
shown in section
"Inverse
0 035
.
0 035
.
+
D
P
characteristics".
1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
(Equation 57)
(Equation 58)
(Equation 59)
(Equation 60)