Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 19
Station communication
19.4.10.5
Table 490:
GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
19.4.10.6
642
Table 489:
GOOSESPRCV Output signals
Name
Type
SPOUT
BOOLEAN
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN

Settings

Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and communication
error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
Description
Single point output
Data valid for single point output
Communication valid for single point output
Test output
Default
Description
Disabled
Operation Disabled/Enabled
Data Value
Data Valid
Updated
1
0
0
0
0
0
0
0
0
0
0
0
0
Updated
1
Updated
1
0
0
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6832-OUTPUTSIGNALS v3
PID-6832-SETTINGS v3
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v4
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
1
0
0
0
1
0
1
1
0
0
Technical manual

Advertisement

Table of Contents
loading

Table of Contents