Access Point - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Section 18
18.1
18.1.1
18.1.2
Table 454:
AP_1 Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Redundancy
None
PRP-0
PRP-1
HSR
IPAddress
0 - 18
SubnetMask
0 - 18
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Ethernet

Access point

Introduction
An access point is an Ethernet communication interface for single or redundant station
communication. Each access point is allocated with one physical Ethernet port, two
physical Ethernet ports are allocated if redundant communication is activated for the
access point.
Device 1
AP1
AP2
SFP_301
SFP_302
IEC16000092 V1 EN-US
Figure 245:
Access points, non redundant (left) and redundant communication
(right)
DHCP is available for the front port, and a device connected to it can thereby obtain an
automatically assigned IP-address.
Settings
Unit
Step
-
-
-
-
IP
1
Address
IP
1
Address
Device 1
AP3
AP1
SFP_303
SFP_301
Default
Description
Disabled
Operation on/off of the access point
None
Ethernet redundancy mode
192.168.1.10
IP address of the access point
255.255.255.0
Subnet mask of the access point
Section 18
Ethernet
GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v1
AP3
AP2
SFP_303
SFP_302
IEC16000092-1-en.vsdx
PID-6775-SETTINGS v4
609