Section 6
Wide area measurement system
112
there are four separate PHASORREPORT blocks including 32 configurable phasor
channels (8 phasor channels in each PHASORREPORT block). Each phasor channel
can be configured as a 3-phase (symmetrical components positive/negative/zero) or
single-phase phasor (A/B/C).
IEC140000119 V2 EN-US
Figure 32:
Multiple instances of PHASORREPORT blocks
Figure
33
shows both instances of ANALOGREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate ANALOGREPORT blocks capable of reporting up to 24 Analog signals
(8 Analog signals in each ANALOGREPORT block). These can include for example
transfer of active and reactive power or reporting the milliampere input signals to the
PDC clients as defined in IEEE C37.118 data frame format.
IEC140000120 V2 EN-US
Figure 33:
Multiple instances of ANALOGREPORT blocks
Figure
34
shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
1MRK 511 408-UUS A
IEC140000119-2-en.vsd
IEC140000120-2-en.vsd
Phasor measurement unit RES670 2.2 ANSI