1MRK 511 408-UUS A
19.4.7.5
Table 481:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
19.4.7.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Table 480:
GOOSEDPRCV Output signals
Name
Type
DPOUT
INTEGER
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN

Settings

Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Incoming data with q=test+oldData
Receiver in block
Receiver in block and communication
error
Receiver in test mode and incoming
data with q= Normal
Receiver in test mode and incoming
data with q= Test
Communication Error
Station communication
Description
Double point output
Data valid for double point output
Communication valid for double point output
Test output
Default
Description
Disabled
Operation Disabled/Enabled
Data Value
Data Valid
Updated
1
0
0
0
0
0
0
0
0
0
0
0
0
Updated
1
Updated
1
0
0
Section 19
PID-6828-OUTPUTSIGNALS v3
PID-6828-SETTINGS v3
GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4
Comm Valid
Test
1
0
1
0
1
0
1
1
1
1
1
0
0
0
1
0
1
1
0
0
635