ABB RES670 Technical Manual page 718

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 19
Station communication
712
Information number is defined for output signals.
Table 542:
I103SUPERV supported functions
Info. no.
Message
32
Measurand supervision I
33
Measurand supervision V
37
I>>back-up operation
38
VT fuse failure
46
Group warning
47
Group alarm
Ground fault indications in monitor direction, I103EF
Indication block for ground fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 543:
I103EF supported indications
INF
Description
51
Ground fault forward
52
Ground fault reverse
Autorecloser indications in monitor direction, I103AR
Indication block for autorecloser in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 544:
I103AR supported indications
INF
Description
16
Autorecloser active
128
CB on by Autorecloser
130
Autorecloser blocked
Function status fault protection for IEC 60870-5-103, I103FLTPROT
Typ
GI
COT
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
1
Y
1,7,9
GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
M11874-199 v8
M11874-363 v6
Technical manual

Advertisement

Table of Contents
loading