Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
15.5.5
Table 248:
WRNCALH Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
15.5.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Name
Type
INPUT14
BOOLEAN
INPUT15
BOOLEAN
INPUT16
BOOLEAN
Table 247:
WRNCALH Output signals
Name
Type
WARNING
BOOLEAN

Settings

Unit
Step
-
-
Operation principle
The logic for group warning WRNCALH block is provided with 16 input signals and 1
WARNING output signal. The function block incorporates internal logic OR gate in
order to provide grouping of connected input signals to the output WARNING signal
from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
WARNING output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
INPUT1
1
INPUT16
ANSI13000192 V1 EN-US
Default
Description
0
Binary input 14
0
Binary input 15
0
Binary input 16
Description
OR function betweeen inputs 1 to 16
Default
Description
Disabled
Operation Disabled/Enabled
200 ms
0
Section 15
Logic
PID-4127-OUTPUTSIGNALS v3
PID-4127-SETTINGS v3
GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2
WARNING
ANSI13000192-1-en.vsd
427