Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
19.4.8.5
Table 484:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
19.4.8.6
Phasor measurement unit RES670 2.2 ANSI
Technical manual
visible and possible to make only if Easy GOOSE engineering is
enabled. For instructions on how to enable Easy GOOSE engineering in
PCM600, refer to the Engineering Manual.
Table 482:
GOOSEINTRCV Input signals
Name
Type
BLOCK
BOOLEAN
SRCINTOUT
INTEGER
Table 483:
GOOSEINTRCV Output signals
Name
Type
INTOUT
INTEGER
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN

Settings

Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Incoming data with q=Normal
Incoming data with q=oldData
Incoming data with q=Invalid
Incoming data with q=test
Table continues on next page
Station communication
Default
Description
0
Block of function
0
Source to integer output
Description
Integer output
Data valid for integer output
Communication valid for integer output
Test output
Default
Description
Disabled
Operation Disabled/Enabled
Data Value
Data Valid
Updated
1
Freeze
0
Freeze
0
Freeze
0
Section 19
PID-6829-INPUTSIGNALS v3
PID-6829-OUTPUTSIGNALS v3
PID-6829-SETTINGS v3
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4
Comm Valid
Test
1
0
1
0
1
0
1
1
637

Advertisement

Table of Contents
loading

Table of Contents