ANSI15000266 V2 EN-US
Figure 54:
OC4 directional release block diagram
Phasor measurement unit RES670 2.2 ANSI
Technical manual
DFWDLx
DFWDLxx
DREVLx
Directional
Element
DREVLxx
Greater
Comparator
Different types of reset time can be selected as described in section
characteristics".
There is a possibility to activate a preset change (MultiPUx, x= 1, 2, 3 or 4) of the set
operation current via a binary input ENMULTx (enable multiplier). In some
applications the operation value needs to be changed, for example due to changed
network switching state.
The operation current value Ix>, is limited to be between Ix>Max and Ix>Min. The
default values of the limits are the same as the setting limits for Ix>, and the limits can
only be used for reducing the allowed range of Ix>. This feature is used when remote
setting of the operation current value is allowed, making it possible to ensure that the
operation value used is reasonable. If Ix> is set outside Ix>Max and Ix>Min, the
closest of the limits to Ix> is used by the function. If Ix>Max is smaller then Ix>Min,
the limits are swapped. The principle of the limitation is shown in Figure 55.
Directional
Release
STLx
xx – means phase to phase 12,23,31
Section 8
Current protection
FORWARD_int
REVERSE_int
Block
x- means three phases 1,2 and 3
ANSI15000266-2-en.vsdx
"Inverse
185