The first LON address in every EVENT function block is found in table 503. The
formula for calculating the LON address is:
LON Address = (EVBlkNr-1)×16 + signalNr +1023
For instance, the first pin at Event block number 2 has the address: (2-1)×16 +1 +1023
= 1040
Table 503:
LON adresses for EVENT functions
Function block
First LON address in
function block
EVENT:1
1024
EVENT:2
1040
EVENT:3
1056
EVENT:4
1072
EVENT:5
1088
EVENT:6
1104
EVENT:7
1120
EVENT:8
1136
EVENT:9
1152
EVENT:10
1168
EVENT:11
1184
EVENT:12
1200
EVENT:13
1216
EVENT:14
1232
EVENT:15
1248
EVENT:16
1264
EVENT:17
1280
EVENT:18
1296
EVENT:19
1312
EVENT:20
1328
Event masks
Event mask for each input can be set individually from Parameter Setting Tool (PST)
under: Settings/IED settings/ Monitoring / Event Function or via parameter setting
tool (PST) as follows: