Measured Value Expander Block Range_Xp - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.8
16.8.1
16.8.2
Phasor measurement unit RES670 2.2 ANSI
Technical manual
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 229:
BINSTATREP logical diagram

Measured value expander block RANGE_XP

Identification
Function description
Measured value expander block
Functionality
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits: low-low limit, low limit, high limit and high-high
limit. The measure value expander block (RANGE_XP) has been introduced to enable
translating the integer output signal from the measuring functions to 5 binary signals:
below low-low limit, below low limit, normal, above high limit or above high-high
limit. The output signals can be used as conditions in the configurable logic or for
alarming purpose.
t
IEC09000732-1-en.vsd
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
Section 16
Monitoring
t
SEMOD52451-1 v2
SEMOD113212-2 v3
ANSI/IEEE C37.2
device number
-
SEMOD52450-4 v7
583