Functionality

Insulation supervision for liquid medium (SSIML (71)) is used for monitoring the
transformer condition. Binary information based on the oil level in the transformer is
used as input signals to the function. In addition, the function generates alarms based
on received information.
Function block
SSIML (71)
BLOCK
LOCKOU T
BLKALM
LVLLO
SENLEVEL
TEMPLO
SENTEMP
ALARM
SENLVLALM
LVLALM
SENLEVELLO
TEMPALM
SETLLO
LEVEL
SETTLO
TEMP
RESETLO
ANSI09000128-2-en.vsdx
ANSI09000128 V2 EN-US
Figure 205:
SSIML (71) function block
Signals
Table 404:
SSIML Input signals
Name
Type
BLOCK
BOOLEAN
BLKALM
BOOLEAN
SENLEVEL
REAL
SENTEMP
REAL
SENLVLALM
BOOLEAN
SENLVLLO
BOOLEAN
SETLLO
BOOLEAN
SETTLO
BOOLEAN
RESETLO
BOOLEAN
Default
Description
0
Block of function
0
Block all the alarms
0.0
Level input from CB
0.0
Temperature of the insulation medium from CB
0
Level alarm signal
0
Level lockout signal
0
Set level lockout
0
Set temperature lockout
0
Reset level and temperature lockout
Section 16
Monitoring
GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v6
GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v2
PID-6951-INPUTSIGNALS v7
529