Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
16.1.5
Table 375:
CVMMXN Non group settings (basic)
Name
Values (Range)
SLowLim
0.0 - 2000.0
SLowLowLim
0.0 - 2000.0
SMin
0.0 - 2000.0
SMax
0.0 - 2000.0
Table continues on next page
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Table 374:
VNMMXU Output signals
Name
Type
VA
REAL
VA_RANGE
INTEGER
VA_ANGL
REAL
VB
REAL
VB_RANGE
INTEGER
VB_ANGL
REAL
VC
REAL
VC_RANGE
INTEGER
VC_ANGL
REAL

Settings

The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in
PCM600.
These six functions are not handled as a group, so parameter settings are only available
in the first setting group.
The following terms are used in the Unit and Description columns:
VBase (VB): Base voltage in primary kV. This voltage is used as reference for
voltage setting. It can be suitable to set this parameter to the rated primary voltage
supervised object.
IBase (IB): Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
supervised object.
SBase (SB): Base setting for power values in MVA.
Unit
Step
%SB
0.1
%SB
0.1
%SB
0.1
%SB
0.1
Description
VA Amplitude, magnitude of reported value
VAAmplitude range
VA Angle, magnitude of reported value
VB Amplitude, magnitude of reported value
VB Amplitude range
VB Angle, magnitude of reported value
VC Amplitude, magnitude of reported value
VC Amplitude range
V_C Angle, magnitude of reported value
Default
Description
80.0
Low limit in % of SBase
60.0
Low Low limit in % of SBase
50.0
Minimum value in % of SBase
200.0
Maximum value in % of SBase
Section 16
Monitoring
PID-6737-OUTPUTSIGNALS v2
SEMOD130322-4 v7
PID-6713-SETTINGS v3
495