Operation Principle - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 22
Basic IED functions
Table 593:
IRIG-B Non group settings (basic)
Name
Values (Range)
SynchType
BNC
Opto
TimeDomain
LocalTime
UTC
Encoding
IRIG-B
1344
1344TZ
TimeZoneAs1344
MinusTZ
PlusTZ
Table 594:
PTP Non group settings (advanced)
Name
Values (Range)
Domain
0 - 127
Priority1
0 - 255
Priority2
0 - 255
22.1.3
22.1.3.1
766
Unit
Step
-
-
-
-
-
-
-
-
Unit
Step
-
1
-
1
-
1

Operation principle

General concepts
Time definitions
The error of a clock is the difference between the actual time of the clock, and the time
the clock is intended to have. Clock accuracy indicates the increase in error, that is, the
time gained or lost by the clock. A disciplined clock knows its own faults and tries to
compensate for them.
Design of the time system (clock synchronization)
The time system is based on a software clock, adjustable from external time sources,
and on a hardware clock. The protection and control modules will be timed from the
hardware clock which is synchronized with the software clock (see Figure 293).
Default
Description
Opto
Type of synchronization
LocalTime
Time domain
IRIG-B
Type of encoding
PlusTZ
Time zone as in 1344 standard
Default
Description
0
0 = Default domain, 1-3 = Alternative domain,
4-127 = User defined
128
The clock with the lowest priority 1 becomes
the reference clock (Grand Master)
128
If all the relevant values for selecting the
reference clock are the same for multiple
devices, the clock with the lowest priority 2 is
selected as the reference clock (Grand
Master)
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-5187-SETTINGS v5
PID-6630-SETTINGS v2
IP12360-1 v4
M11346-77 v1
M11346-80 v3
GUID-E2B9E81C-5733-4521-B27F-BF33E05CCFB0 v8
Technical manual