ABB RES670 Technical Manual page 504

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 16
Monitoring
Name
Values (Range)
QDbRepInt
1 - 100000
QZeroDb
0 - 100000
QHiHiLim
-2000.0 - 2000.0
QHiLim
-2000.0 - 2000.0
QLowLim
-2000.0 - 2000.0
QLowLowLim
-2000.0 - 2000.0
QLimHyst
0.000 - 100.000
PFDbRepInt
1 - 100000
PFZeroDb
0 - 100000
PFHiHiLim
-1.000 - 1.000
PFHiLim
-1.000 - 1.000
PFLowLim
-1.000 - 1.000
PFLowLowLim
-1.000 - 1.000
PFLimHyst
VDbRepInt
VZeroDb
VHiHiLim
VHiLim
VLowLim
VLowLowLim
VLimHyst
IDbRepInt
IZeroDb
IHiHiLim
IHiLim
ILowLim
ILowLowLim
ILimHyst
Table continues on next page
498
Unit
Type
m%
%SB
%SB
%SB
%SB
%
Type
m%
-
-
-
-
0.000 - 100.000
%
1 - 100000
Type
0 - 100000
m%
0.0 - 200.0
%VB
0.0 - 200.0
%VB
0.0 - 200.0
%VB
0.0 - 200.0
%VB
0.000 - 100.000
%
1 - 100000
Type
0 - 100000
m%
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.0 - 500.0
%IB
0.000 - 100.000
%
Step
Default
1
10
500
1000
0.1
150.0
0.1
120.0
0.1
-120.0
0.1
-150.0
0.001
5.000
1
10
100
500
0.001
1.000
0.001
0.800
0.001
-0.800
0.001
-1.000
0.001
5.000
1
10
500
1000
0.1
150.0
0.1
120.0
0.1
80.0
0.1
60.0
0.001
5.000
1
10
500
1000
0.1
150.0
0.1
120.0
0.1
80.0
0.1
60.0
0.001
5.000
1MRK 511 408-UUS A
Description
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range, common for
all limits
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range, common for
all limits
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Hysteresis value in % of range, common for
all limits
Cycl: Report interval (s), Db: In 0,001% of
range, Int Db: In 0,001%s
Magnitude zero point clamping in 0,001% of
range
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range, common for
all limits
Phasor measurement unit RES670 2.2 ANSI