ABB RES670 Technical Manual page 181

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

1MRK 511 408-UUS A
Name
Values (Range)
Pickup3
5 - 2500
t3
0.000 - 60.000
TD3
0.05 - 999.00
IMin3
1 - 10000
t3Min
0.000 - 60.000
MultPU3
1.0 - 10.0
DirModeSel4
Disabled
Non-directional
Forward
Reverse
Characterist4
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Pickup4
5 - 2500
t4
0.000 - 60.000
TD4
0.05 - 999.00
IMin4
1 - 10000
t4Min
0.000 - 60.000
MultPU4
1.0 - 10.0
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Unit
Step
Default
%IB
1
250
s
0.001
0.800
-
0.01
0.05
%IB
1
33
s
0.001
0.000
-
0.1
2.0
-
-
Non-directional
-
-
ANSI Def. Time
%IB
1
175
s
0.001
2.000
-
0.01
0.05
%IB
1
17
s
0.001
0.000
-
0.1
2.0
Current protection
Description
Operating phase current level for step 3 in %
of IBase
Def time delay or add time delay for inverse
char of step 3
Time multiplier for the inverse time delay for
step 3
Minimum operate current for step3 in % of
IBase
Minimum operate time for inverse curves for
step 3
Multiplier for current operate level for step 3
Directional mode of step 4 (Disabled, Nondir,
Forward, Reverse)
Selection of time delay curve type for step 4
Operating phase current level for step 4 in %
of IBase
Def time delay or add time delay for inverse
char of step 4
Time dial multiplier for the inverse time delay
for step 4
Minimum operate current for step4 in % of
IBase
Minimum operate time for inverse curves for
step 4
Multiplier for current operate level for step 4
Section 8