Signals

Signals are available in the Signal Matrix Tool (SMT) and as hardware
channels in the Application Configuration Tool (ACT).
Table 557:
LDCMRecBinStat1 Output signals
Name
Type
COMFAIL
BOOLEAN
ADDRERR
BOOLEAN
CRCERROR
BOOLEAN
REMBLKDF
BOOLEAN
NOCARR
BOOLEAN
NOMESS
BOOLEAN
LNGTHERR
BOOLEAN
YBIT
BOOLEAN
LOWLEVEL
BOOLEAN
Table 558:
LDCMRecBinStat2 Output signals
Name
Type
CH1
STRING
CH2
STRING
CH3
STRING
CH4
STRING
COMFAIL
BOOLEAN
COMALM
BOOLEAN
BLKDIFF
BOOLEAN
ADDRERR
BOOLEAN
RED_ACT
BOOLEAN
CRCERROR
BOOLEAN
TRDELERR
BOOLEAN
SYNCERR
BOOLEAN
REMBLKDF
BOOLEAN
Table continues on next page
GUID-0918C53D-F755-4FA1-BB3C-F672AFC6A7D2 v1
Description
Detected error in the differential communication
Incoming message from non-valid address
Identified error by CRC check in incoming message
Remote terminal indicates diff protection is blocked
No carrier is detected in the incoming message
No start and stop flags identified for the incoming
message
Wrong length of the incoming message
Detected error in remote end with incoming message
Low signal level on the receive link
Description
Remote communication channel 1
Remote communication channel 2
Remote communication channel 3
Remote communication channel 4
Detected error in the differential communication
Delayed alarm signal for communication failure
Link error, values are substituted, diff protection is
blocked
Incoming message from non-valid address
Redundant channel active
Identified error by CRC check in incoming message
Transmission time is longer than permitted
Error in echo synchronization
Remote terminal indicates diff protection is blocked
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6471-OUTPUTSIGNALS v2