1MRK 511 408-UUS A
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Record no. N
General dist.
Information & Setting
Indications
infotrmation
ANSI05000161 V2 EN-US
Figure 224:
Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded
when the memory is full, the oldest disturbance report is overwritten by the new one.
The total recording capacity for the disturbance recorder is depending of sampling
frequency, number of analog and binary channels and recording time and settings
information. Figure
225
time tested for a typical configuration, that is, in a 60 Hz system it is possible to record
80 where the average recording time is 3.4 seconds. The memory limit does not affect
the rest of the disturbance report (Event list (EL), Event recorder (ER), Indications
(IND) and Trip value recorder (TVR)).
Number of recordings
100
3.4s
80
60
40
250
ANSI05000488 V1 EN-US
Figure 225:
Example of number of recordings versus the total recording time
Disturbance report
Record no. N+1
Trip
Event
values
recordings
shows the number of recordings versus the total recording
3.4s
40 analog
96 binary
6.3s
60 Hz
300
Section 16
Monitoring
Record no. N+100
Disturbance
recording
ANSI05000161-2-en.vsdx
20 analog
96 binary
6.3s
6.3s
50 Hz
Total recording time
350
en05000488_ansi.vsd
Event list
(SOE)
400 s