Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 7
Impedance protection
7.2.5
Table 85:
OOSPPAM (78) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationZ1
Disabled
Enabled
ReachZ1
1.00 - 100.00
OperationZ2
Disabled
Enabled
tBreaker
0.000 - 1.000
156
Table 84:
OOSPPAM (78) Output signals
Name
Type
TRIP
BOOLEAN
TRIPZ1
BOOLEAN
TRIPZ2
BOOLEAN
PICKUP
BOOLEAN
GENMODE
BOOLEAN
MOTMODE
BOOLEAN
R
REAL
X
REAL
SLIPFREQ
REAL
ROTORANG
REAL
VCOSPHI
REAL

Settings

Unit
Step
-
-
-
-
% ZFw
0.01
-
-
s
0.001
Description
Common trip, issued when either zone 1 or zone 2 trip
Zone 1 trip
Zone 2 trip
Set when measured impedance enters lens
characteristic
Generator rotates faster than the system during pole
slip
Generator rotates slower than the system during pole
slip
Real part of measured positive-sequence impedance
% of VBase/(sqrt(3)*IBase)
Imaginary part of measured positive-seq impedance %
of VBase/(sqrt(3)*IBase)
Slip frequency in Hz
Rotor angle as estimated by the out-of-step function
Estimated Ucos(Phi) voltage during pole slip, in V
Default
Description
Disabled
Operation Disabled/Enabled
Enabled
Operation Zone1 Enable/Disable
50.00
Percentage part of total forward impedance;
defines Z1 reach
Enabled
Operation Z2 Enable/Disable
0.040
Breaker opening time; use default 0s value if
it is unknown
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-3539-OUTPUTSIGNALS v10
PID-3539-SETTINGS v10
Technical manual