Directional phase overcurrent protection, four steps
OC4PTOC(51_67)
Identification
Function description
Directional phase overcurrent
protection, four steps
Functionality
Directional phase overcurrent protection, four steps OC4PTOC (51/67) has
independent inverse time delay settings for steps 1 to 4.
All IEC and ANSI inverse time characteristics are available together with an optional
user defined time characteristic.
The directional function needs voltage as it is voltage polarized with memory. The
function can be set to be directional or non-directional independently for each of the
steps.
A second harmonic blocking level can be set for the function and can be used to block
each step individually.