Settings - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 14
Control
14.1.5
Table 213:
SLGAPC Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
NrPos
2 - 32
OutType
Pulsed
Steady
tPulse
0.000 - 60.000
tDelay
0.000 - 60000.000
StopAtExtremes
Disabled
Enabled
14.1.6
14.1.7
384

Settings

Unit
Step
-
-
-
1
-
-
s
0.001
s
0.010
-
-
Monitored data
Table 214:
SLGAPC Monitored data
Name
Type
SWPOSN
INTEGER
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGAPC)
function has two operating inputs – UP and DOWN. When a signal is received on the
UP input, the function will activate the output next to the present activated output, in
ascending order (for example if the present activated output is P03 and one activates
the UP input then the output P04 will be activated). When a signal is received on the
DOWN input, the function will activate the output next to the present activated output,
in descending order (for example if the present activated output is P03 and one
activates the DOWN input then the output P02 will be activated). Depending on the
output settings the output signals can be steady or pulsed. In case of steady signals, the
output will be active till the time it receives next operation of UP/DOWN inputs. Also,
depending on the settings one can have a time delay between activation of the UP or
DOWN input signals and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration Tool, there are other possibilities that will allow an user to set the
desired position directly (without activating the intermediate positions), either locally
or remotely, using a "select before execute" dialog. One can block the function
operation, by activating the BLOCK input. In this case, the present position will be
Default
Description
Disabled
Operation Disabled/Enabled
32
Number of positions in the switch
Steady
Output type, steady or pulse
0.200
Operate pulse duration, in [s]
0.000
Time delay on the output, in [s]
Disabled
Stop when min or max position is reached
Values (Range)
Unit
-
-
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
PID-6641-SETTINGS v3
PID-6641-MONITOREDDATA v3
Description
Switch position (integer)
SEMOD114931-4 v7
Technical manual