can be used for blocking the alarms, and the BLOCK input can block both alarm and
the lockout indications.
The output ALARM goes high if the level alarm condition or the temperature alarm
condition exists in the transformer. The output ALARM can be blocked by activating
BLOCK or BLKALM inputs.
The output LOCKOUT goes high if the pressure lockout condition or the temperature
lockout condition exists in the transformer and it resets by using the binary input
RESETLO. The output LOCKOUT can be blocked by activating BLOCK input.

Technical data

Table 408:
SSIML(71) Technical data
Function
Oil alarm level
Oil lockout level
Temperature alarm level
Temperature lockout level
Time delay for oil alarm
Reset time delay for oil alarm
Time delay for oil lockout
Time delay for temperature alarm
Reset time delay for temperature
alarm
Time delay for temperature
lockout
Breaker monitoring SSCBR
Identification
Function description
Breaker monitoring
Range or value
1.00-100.00
1.00-100.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
IEC 61850
IEC 60617
identification
identification
SSCBR
-
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7
Accuracy
±10.0% of set value
±10.0% of set value
±2.5% of set value
±2.5% of set value
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
±0.2% or ±250ms whichever is
greater
GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7
ANSI/IEEE C37.2
device number
-
Technical manual