Identification - ABB RES670 Technical Manual

Relion 670 series, phasor measurement unit
Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Section 19
Station communication
19.7.13.2
19.7.13.3
19.7.13.4
704
The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2
steady ON/OFF outputs. The ON output is pulsed with a command with value 2, while
the OFF output is pulsed with a command value 1. If in steady mode is ON asserted
and OFF deasserted with command 2 and vice versa with command 1. Steady mode is
selected by setting PulseLength=0. The I103GENCMD is retained, and a command in
steady mode will be reissued on restart.

Identification

Function description
Function commands generic for IEC
60870-5-103
Function block
I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285-1-en.vsd
IEC10000285 V1 EN-US
Figure 279:
I103GENCMD function block
Signals
Table 530:
I103GENCMD Input signals
Name
Type
BLOCK
BOOLEAN
Table 531:
I103GENCMD Output signals
Name
Type
CMD_OFF
BOOLEAN
CMD_ON
BOOLEAN
Function block
IEC 60617
name
identification
I103GENCMD
-
Default
Description
0
Block of command
Description
Command output OFF
Command output ON
Phasor measurement unit RES670 2.2 ANSI
1MRK 511 408-UUS A
GUID-1933A30C-5214-4116-8CD3-91BD975FACED v1
ANSI/IEEE C37.2
device number
-
GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1
PID-3970-INPUTSIGNALS v5
PID-3970-OUTPUTSIGNALS v5
Technical manual